Troubleshooting
| Error Description | Possible Causes | Fix |
|
The battery failed |
The battery is highly sulfated. The charger is connected to a six-volt battery. |
Replace the battery with a 12-volt deep-cycle marine battery. |
|
Battery over-voltage |
The charger is connected to a 24 volt battery. |
Replace the battery with a 12-volt deep-cycle marine battery |
|
Charge time monitor |
Battery took too long to complete its charge: |
A: Be sure the pump cannot start during charging; reset the charger. |
|
Excessive battery drain |
Pump motor ran during charging (that is, with the |
Check primary sump pump. The BBU generally runs only |
|
Reverse battery connection |
Charger is connected backwards to the battery. |
Reconnect charger (+) to battery (-)/(-) to (-). |
|
Battery overheated |
Cells in an old battery may deteriorate with age. |
Replace the battery with a 12-volt deep-cycle marine battery. |
|
Charging error |
An internal error occurred in the charger during one |
Unplug the charger for 10 seconds and then plug it in again. If error occurs again, refer to table below. |
Error Light Indications
Note: This chart identifies light codes indicating various charger error modes. It only applies when the ‘Charger Mode’ light flashes yellow/green alternately. The light codes listed here do not relate.
“Silence Alarm/Reset” Rocker Switch: Push the left side of the rocker switch on the front of the charger to silence the alarm.
Note: This will not silence the alarm when the battery is below 8.2 volts or the system is in error mode.
The front of the charger has the LED status lights: A.C. Power, Pump Run Status, Alarm Silence, Battery Status and Charger Mode. The status lights only apply when the ‘Charger Mode’ light is not flashing yellow/green. The ‘Pump System Status’ LED stays lit after the back-up pump has cycled. To reset an error light, push the right side of the rocker switch, located under the LED legend, to the right. When you reset the system, the charger will start its diagnostic procedure (pre-qualification test, etc.) from the beginning. If the cause of the error mode is not corrected, the system will go into the error mode again.
LED Error Modes
| A.C. Power Status | Pump Run Status | Alarm Silence | Charge Mode | Error Mode |
|
Flashing |
Off |
Off |
Flashing Yellow/Green |
Battery Overheated |
|
Flashing |
Off |
Flashing |
Flashing Yellow/Green |
Charge Time Monitor |
|
Flashing |
Flashing |
Off |
Flashing Yellow/Green |
Excessive Battery Drain |
|
Flashing |
Flashing |
Flashing |
Flashing Yellow/Green |
Failed Pre-Qualification Test |
|
Off |
Off |
Flashing |
Flashing Yellow/Green |
Battery Over-Voltage |
|
Off |
Flashing |
Off |
Flashing Yellow/Green |
Reverse Battery Connection |
|
Off |
Flashing |
Flashing |
Flashing Yellow/Green |
Output Over-Current |
Alarm Summary
| Charger Light | On/Off/Flashing | Alarm Buzzer | Indicates |
|
All LEDs |
Flash ONCE |
Off |
Connected system to AC power or to battery; or, pressed ‘Reset’ when in ERROR mode |
|
AC Power Status |
On |
Off |
System is receiving AC power |
|
Pump Run Status |
Fast Flash (2x/second) Slow Flash (1x/2 seconds) |
Beep in synch |
Pump is running. Press LEFT side of rocker switch |
|
Alarm Silence |
On |
Alarm is silenced |
|
|
Battery Status |
On Slow Flash Off |
Off On Off |
System is not connected to a battery or is connected to a battery charged to less than 1 volt DC |
|
Charger Mode |
Slow YELLOW Flash Solid YELLOW Flash Fast YELLOW Flash Solid GREEN |
Off Off Off Off |
System is in “pre-qualification” stage. This will last from 1 minute to 5 hours, depending on the condition of your battery. System is in the “Constant Current Charge” stage. This will continue until the battery voltage reaches approximately 14.3 volts. System is in the “Constant Voltage Charge” stage. This could last up to 14.5 hours until battery is fully charged. |
Audio Alarm Indications
| Charger Light | On/Off/Flashing | Alarm Buzzer | Indicates |
|
On - Beeping |
Slow beep in synch with ‘Battery |
Battery is down to |
Investigate cause; battery is very low. You have limited |
|
On - Beeping |
Fast beep in sync from ‘Battery |
Battery is down to |
Investigate cause; battery is nearly dead. You have almost no pump run time left. Alarm CANNOT be silenced |
|
On - Beeping |
Fast beep in synch with one or more of the ‘AC Power Status’, ‘Pump Run Status’, or ‘Alarm Silence’ LEDs and with the ‘Charger Mode’ LED flashing alternately YELLOW/GREEN |
System is in ERROR |
Refer to ERROR Light Indicatons above. |
|
On - Beeping |
Fast beep in synch with ‘Pump Run |
Pump is running |
None. Alarm will stop when pump stops running. To silence alarm, press and release LEFT side of toggle switch |