Ion 2100DC Backup System Troubleshooting

Troubleshooting

Error Description Possible Causes Fix

The battery failed
pre-qualification test

The battery is highly sulfated. The charger is connected to a six-volt battery.

Replace the battery with a 12-volt deep-cycle marine battery.

Battery over-voltage

The charger is connected to a 24 volt battery.

Replace the battery with a 12-volt deep-cycle marine battery

Charge time monitor

Battery took too long to complete its charge:
A. Load applied (e.g. the pump motor started) during charging.
B. The battery ampere-hour rating is too large (max. 130 ampere-hours).

A: Be sure the pump cannot start during charging; reset the charger.
B: Replace with correct size battery.

Excessive battery drain

Pump motor ran during charging (that is, with the
main A.C. power ON), causing the system to shut
down.

Check primary sump pump. The BBU generally runs only
when the main A.C. power is out. If there has not been any power outage and the BBU has run, the primary pump itself may have failed.

Reverse battery connection

Charger is connected backwards to the battery.
(That is, charger (+) to battery (-) and vice versa).

Reconnect charger (+) to battery (-)/(-) to (-).

Battery overheated

Cells in an old battery may deteriorate with age.

Replace the battery with a 12-volt deep-cycle marine battery.

Charging error

An internal error occurred in the charger during one
of the charging states.

Unplug the charger for 10 seconds and then plug it in again. If error occurs again, refer to table below.

Error Light Indications

Note: This chart identifies light codes indicating various charger error modes. It only applies when the ‘Charger Mode’ light flashes yellow/green alternately. The light codes listed here do not relate.

“Silence Alarm/Reset” Rocker Switch: Push the left side of the rocker switch on the front of the charger to silence the alarm.

Note: This will not silence the alarm when the battery is below 8.2 volts or the system is in error mode.

The front of the charger has the LED status lights: A.C. Power, Pump Run Status, Alarm Silence, Battery Status and Charger Mode. The status lights only apply when the ‘Charger Mode’ light is not flashing yellow/green. The ‘Pump System Status’ LED stays lit after the back-up pump has cycled. To reset an error light, push the right side of the rocker switch, located under the LED legend, to the right. When you reset the system, the charger will start its diagnostic procedure (pre-qualification test, etc.) from the beginning. If the cause of the error mode is not corrected, the system will go into the error mode again.

LED Error Modes

A.C. Power Status Pump Run Status Alarm Silence Charge Mode Error Mode

Flashing

Off

Off

Flashing Yellow/Green

Battery Overheated

Flashing

Off

Flashing

Flashing Yellow/Green

Charge Time Monitor

Flashing

Flashing

Off

Flashing Yellow/Green

Excessive Battery Drain

Flashing

Flashing

Flashing

Flashing Yellow/Green

Failed Pre-Qualification Test

Off

Off

Flashing

Flashing Yellow/Green

Battery Over-Voltage

Off

Flashing

Off

Flashing Yellow/Green

Reverse Battery Connection

Off

Flashing

Flashing

Flashing Yellow/Green

Output Over-Current

Alarm Summary

Charger Light On/Off/Flashing Alarm Buzzer Indicates

All LEDs

Flash ONCE

Off

Connected system to AC power or to battery; or, pressed ‘Reset’ when in ERROR mode

AC Power Status

On
Very Slow Flash

Off
Off

System is receiving AC power
System is not receiving AC power

Pump Run Status

Fast Flash (2x/second)

Slow Flash (1x/2 seconds)
Off

Beep in synch
with LED Flash
Off
Off

Pump is running. Press LEFT side of rocker switch
to silence alarm
Pump has run, but is not running now
Pump has not run

Alarm Silence

On
Off

Alarm is silenced
Alarm is active

Battery Status

On

Slow Flash
Fast Flash

Off

Off

On
On

Off

System is not connected to a battery or is connected to a battery charged to less than 1 volt DC
Battery voltage less than 10.9 volts. Alarm can be silenced
Battery voltage is less than 8.2 volts. Alarm CANNOT
be silenced
System is properly connected to a battery

Charger Mode

Slow YELLOW Flash

Solid YELLOW Flash

Fast YELLOW Flash

Solid GREEN
Flashing alternately YELLOW/
GREEN

Off

Off

Off

Off
On - Beeping

System is in “pre-qualification” stage. This will last from 1 minute to 5 hours, depending on the condition of your battery. System is in the “Constant Current Charge” stage. This will continue until the battery voltage reaches approximately 14.3 volts.

System is in the “Constant Voltage Charge” stage. This could last up to 14.5 hours until battery is fully charged.

System is in ERROR mode. Alarm will beep in synch with one or more of the ‘AC Power Status’, ‘Pump Run Status’, or ‘Alarm Silence’ LEDs.

Audio Alarm Indications

Charger Light On/Off/Flashing Alarm Buzzer Indicates

On - Beeping

Slow beep in synch with ‘Battery
Status’ LED

Battery is down to
about 10.9 volts

Investigate cause; battery is very low. You have limited
pump run time left. Press and release LEFT side of toggle switch to silence alarm.

On - Beeping

Fast beep in sync from ‘Battery
Status’ LED

Battery is down to
about 8.2 volts

Investigate cause; battery is nearly dead. You have almost no pump run time left. Alarm CANNOT be silenced

On - Beeping

Fast beep in synch with one or more of the ‘AC Power Status’, ‘Pump Run Status’, or ‘Alarm Silence’ LEDs and with the ‘Charger Mode’ LED flashing alternately YELLOW/GREEN

System is in ERROR
mode

Refer to ERROR Light Indicatons above.

On - Beeping

Fast beep in synch with ‘Pump Run
Status’ LED

Pump is running

None. Alarm will stop when pump stops running. To silence alarm, press and release LEFT side of toggle switch